Numerical simulation of wind load on cooling towers under double-tower condition

SHEN Guo-hui,LIU Ruo-fei,Bingnan Sun
2007-01-01
Abstract:Computational fluid dynamics(CFD) method was employed to clarify the interference effect of double cooling towers with different tower distance and wind azimuth.The wind load on single tower was obtained by CFD simulation,and the caparison of the simulation results with the Codes verified the rationality of CFD method.The simulation of double-tower implies that the drag coefficient of rear tower increases with increasing wind azimuth and reaches maximum value at side-to-side arrangement under fixed towers' distance.When two towers are arranged in tandem,the drag coefficient of rear tower increases with increasing towers' distance,and inclines to the results of single tower.The towers' distance of 1.1—1.4 times of tower base diameter at side-to-side arrangement should be avoided due to the worst interference effect.