Interference effect of wind-induced response on large hyperbolic cooling tower

SHEN Guo-hui,YU Guan-peng,SUN Bing-nan,LOU Wen-juan,LI Qing-xiang,YANG Shi-chao
DOI: https://doi.org/10.3785/j.issn.1008-973X.2012.01.06
2012-01-01
Abstract:The interference effect between three cooling towers that are arranged in reverse triangle was analyzed as a simplified model in order to investigate the grouping effect of wind loadings acting on Ferrybridge cooling towers.For three towers condition,180 wind tunnel tests with respect to tower distance and wind azimuth were conducted.The wind induced responses based on the test results were calculated and the interference effect for 180 test conditions was analyzed.Then the referenced interference values for the Ferrybridge cooling towers were given.Results showed that the mean value of base shear coefficient in the crosswind direction was nearly zero,whereas the peak value was large under the isolated tower condition.The tensile stresses on the tower shell under wind loading were mainly located on the middle and lower parts of the shell.For the three towers condition,the interference factors of the latitudinal membrane stress were all less than 1,whereas the interference factors of the peak meridian membrane stress were mostly bigger than 1 with the biggest value reaching 1.57.
What problem does this paper attempt to address?