Experimental Research on Switching Electro-magnetic Transient Characteristics of Converter Valves in HVDC Converter Stations

Zhan-qing YU,Jin-liang HE,Rong ZENG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.03.025
2011-01-01
Abstract:Electromagnetic transient of valves in HVDC converters during turn-on and turn-off processes is the major factor for steady state electromagnetic disturbance(EMD) which is considered in analysis and grading devices design.Consequently,a measuring system for electromagnetic transient research was established.Transient waveforms of voltage across valve,current through it and magnetic field near it were gained during the valve operation.The spectra of voltage,current and magnetic field were analyzed.Influences of operating voltage,current and junction temperature on switching transients were studied.Results show that voltage changes exponentially during turn-on process,and the turn-on time is about several micro seconds.Turn-on time rises with increasing of operating voltage,current and junction temperature,the change amplitudes are up to 20%.Influences of operating voltage and junction temperature on turn-off time are not obvious.Therefore,the influences of operating parameters on turn-on and turn-off should be considered.
What problem does this paper attempt to address?