Digitally controlled UPS inverter with dead time and output current compensation

LIU Yadong,XING Yan,HUANG Lipei
DOI: https://doi.org/10.3321/j.issn:1000-0054.2006.01.005
2006-01-01
Abstract:A digital control scheme was developed to improve the output performance of UPS(uninterruptable power supply) inverters without adding additional sensors.The scheme uses feed forward compensations for the dead time effect for a linear load which is equivalent to a voltage disturbance of the square wave based on the average-area method and for the output current regarded as disturbance.The output filter capacitor current comes from the differential to the output voltage to give quasi double loop control without current sensor.The total harmonics distortion(THD) for a 1 KVA prototype at rated resistor load is 2.49% with the voltage regulation for a step change from null load to rated load of 6.75%.The results show that the dead time compensation and output current compensation is quite effective.