Research on UPS Based on DSP Dual-loop Control

Hao Ma
2006-01-01
Abstract:A 5 kVA on-line digital controlled UPS based on DSP is presented. To improve the steady state operation and dynamic response, a dual-loop control strategy which incorporates the inductor current and the instantaneous output voltage has been used. The system based on Infineon XC164CM DSP that controls the inverter and the system logic operation is introduced. The power part of the UPS consists of Infineon F4-100R06KL4 IGBT module. The experimental result is given and has proved the design is correct.
What problem does this paper attempt to address?