Phase Selection Element Based on Phase Relationship Between Sequence Components of Faulty Branch Current

LIU Kai,SUONAN Jiale
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.03.013
2013-01-01
Abstract:The phase relationship between the positive sequence and negative sequence components of faultybranch current contains clear information of fault,but it is easily influenced by the current distributioncoefficient.The negative sequence component of differential current is inphase with that of faulty branchcurrent.After the positive sequence component of differential current is subtracted by the positive sequencecapacitive current caused by system power sources,it becomes inphase with the positive sequence componentof the faulty branch current.The faulty phase can thus be selected according to the phase relationshipbetween the positive sequence components of modified differential current and the negative components.Being highly sensitive and available during whole fault period,the proposed phase selection element isimmune to the distributed line capacitance,line compensation reactor and current distribution coefficient.Simulative results show its validity.