Fault line selection for four-parallel lines on same tower based on circulation currents

XU Peng,WANG Gang,LI Hai-feng,HUANG Jun-kai,WU Ji-yang
DOI: https://doi.org/10.3969/j.issn.1674-3415.2011.03.015
2011-01-01
Abstract:In order to eliminate the coupling effects between four-parallel transmission lines,t his paper proposes a new phase-mode transformation method for four-parallel transmission lines on same tower based on matrix transformation analysis by decoupling mutual inductances between different lines first and then decoupling mutual inductances between different phases. Based on boundary conditions of single-circuit line fault,t he phase relationship between sequence circulation componentsare deduced for different circuit lines faults. And the characteristicsthat phase-angle difference between the circulation current components is 90°at least are used to propose a new method for fault line selection of four-parallel transmission lines on same tower. The proposed method is not affected by system impedances. A large number of simulations based on ATP/EMTP prove the proposed method's correctness ant effectiveness.
What problem does this paper attempt to address?