Simulation Study of Series Resonance Type Fault Current Limiter
Dao-zhuo JIANG,Hang-yin MAO,Zhi-xiang AO,Zhao-lin WU
DOI: https://doi.org/10.3969/j.issn.1674-3415.2010.23.030
2010-01-01
Abstract:The series resonance type fault current limiter has the advantages of simple operating principle and topological structure,etc. The primary parameter of series resonance type fault current limiter for high-voltage system is reasonable.However,in the process of restraining fault current after a fault occurrence in electrical network,the capacitor and parallel inverter switch will confront poor working condition.This paper studies the above condition by simulation using the software Matlab.Proceeding from the study,we arrive at the conclusions:1)in the process of closing the inverter switch short circuit capacitor to make the current limiter work in short circuit current limiting mode switching from normal operation mode,there is higher-order of voltage(current)oscillation between capacitor and parallel inverter switch,and the peak value of voltage(current)increases and oscillates with the growing of the speed for closing the inverter switch; 2)when the inverter switch is composed of semiconductor device,control system must respond to short circuit and close the inverter switch quickly,otherwise,the semiconductor device may be damaged by over current(voltage);3)during fault current limiter working in current limiting mode to short circuit loop being shut off by relay protection device,the inverter switch will bear the full fault current and oscillation current.If using semiconductor device as inverter switch,the capacity of semiconductor device must be chosen according to the working condition.