Experimental study of double direct contact ice slurry generator

Zhang Xuejun,Wang Lingshi
DOI: https://doi.org/10.3969/j.issn.1009-8402.2011.05.024
2011-01-01
Abstract:Studies the heat transfer process and the performance of a direct contact ice slurry generator.By fitting the experimental data,obtains an empirical formula of volumetric heat transfer coefficient,from which the calculation values agree with the experimental values well with a relative error less than 15%.Based on the empirical formula,establishes a laboratory-scale double direct contact ice slurry generator.If the air flow rate is fixed at 200 m3/h,the ice production rate will be 0.091 kg/min.The experimental results also show that the cold energy consumption of the fan accounts for more than half of the total amount.In order to improve the system energy efficiency coefficient,it is necessary to strengthen the air pipes insulation and increase the solution thermal capacity,and also is appropriate to utilize the free cold energy of LNG.