Study on the treatment of ammonia nitrogen secondary effluent with the biological aerated filter

Dong Wang,Hesheng Li,Dehua Liu
DOI: https://doi.org/10.3969/j.issn.1005-829X.2005.12.014
2005-01-01
Abstract:Secondary effluent of West Zone Wastewater Treatment Plant of Yanshan Petrochemical Co.has been treated with the biological aerated filter process.Its effects on NH3-N removal of NH3-N and COD concentration,COD/NH3-N ratio and alkalinity of influent and the ratio of gas and water of the system are studied.The results showthat biological aerated filter could remove NH3-N perfectly when NH3-N concentration of influent is below 30 mg/L.The average NH3-N removal efficiency reaches 90.4%,and NH3-N concentration of effluent is below 1 mg/L.NH3-N removal efficiency decreases with the increase of COD/NH3-N ratio of influent and is higher when COD/NH3-N ratio is below2.0.Higher NH3-N removal efficiency has been got by using the process with alkalinity approximately being 290 mg/L and the ratio of air and water being 3∶1.
What problem does this paper attempt to address?