Detection Methods of the Faulty Porcelain Insulators

Li Li-xue,Jiang Xiu-chen
2006-01-01
Abstract:The present on-line detection methods of the porcelain insulator are reviewed in this paper. A new synthetic method, which includes three new methods, is introduced in detail. The first method is the sensitive insulator method that is based on 110kV and 220kV power line. In this method it is proved that the fourth insulator numbered from the earth side is generally the sensitive insulator. Only via measuring its distribution voltage can we know whether there is a faulty insulator in the string or not. The second method is called pulse current method. This method points to the condition that the faulty insulator has a discharge track, but can still afford high distribution voltage. The discharge pulse can be extracted from the noises effectively by wavelet. The third method is called string current method. It is proved that for 110kV line, the string current will increase when there is a faulty insulator in the string. With this synthetic method, the correction ratio of the judgment will be enhanced and the workload of measurement will be decreased greatly.