Study on Fire Hazard of Pre-Aging and Post-Aging PVC Cable Materials

Zai-hui LI,Yuan HU,Lei SONG,Xin WANG,Hao FENG,Gan-xin JIE
DOI: https://doi.org/10.3969/j.issn.1004-5309.2011.01.009
2011-01-01
Fire Safety Science
Abstract:The fire hazard of pre-aging and post-aging PVC cable materials was investigated using microscale combustion calorimetry(MCC),thermogravimetric analysis(TGA),thermogravimetric analysis-infrared spectrometry(TG-FTIR) and real time FTIR.MCC data indicated that the peak heat release rate(PHRR) of post-aging PVC cable materials increased by 56.3% compared to pre-aging PVC cable materials,the total heat release increased from 10.6 kJ/g to 16.8kJ/g and the ignition temperature decreased from 302℃ to 282℃.The TG-FTIR and RTFTIR results suggested that the main pyrolysis products of PVC cable materials were water,hydrocarbons,CO2,CO,et al.The maximum decomposition rate of PVC cable materials appeared at around 240℃,which corresponded well with MCC and TGA.The pyrolysis products of PVC cable materials contained CO2,CO and toxic HCl.It is concluded that the fire hazard of PVC cable materials increases during the course of use.
What problem does this paper attempt to address?