Dependence of partial discharge characteristics at spacer surface on particle size in SF6 gas insulated system

N. Hayakawa,T. Okusu,K. Nishizawa,H. Kojima,F. Endo,M. Yoshida,K. Uchida,H. Okubo
DOI: https://doi.org/10.1109/CMD.2008.4580227
2008-04-21
Abstract:A metallic particle appeared in a gas insulated switchgear (GIS) sometimes adheres on a solid spacer surface. If the adhered metallic particle is exposed to a surge high voltage, a breakdown (BD) may be induced. Therefore, it is eagerly demanded to diagnose its risk correctly under the service voltage by partial discharge (PD) measurement. In this paper, particle-initiated surface PD characteristics were systematically studied in 0.4 MPa SF6 gas by changing the sizes of particles. PD inception voltage (PDIV), temporal change of PD current and the PD pulse number were analyzed in detail. Furthermore, comparing with PD characteristics of particles in a gas gap, the influence of the solid insulator on the PD characteristics was clarified. It was found out that PD characteristics greatly changed with time owing to electric charges deposited on a spacer surface.
What problem does this paper attempt to address?