Electro-thermal analysis and dynamic arc parameters evaluation in multi chamber arrester under structural and dimensional changes effect using the finite element method

Kimiya Silakhori,Mohammad Mirzaie,Iraj Ahmadi
DOI: https://doi.org/10.1016/j.epsr.2024.110185
IF: 3.818
2024-01-31
Electric Power Systems Research
Abstract:In order to improve the ability to extinguish the arc caused by lightning surge overvoltage, a type of smart arrester, known as multi-chamber arrester (MCA), has been developed. These arresters are used as lightning protection devices to protect the transmission and distribution lines. In this paper, a two-dimensional mathematical transient model of the MCA is presented using the finite element method (FEM). This model serves as the foundation for investigating the arc motion characteristics of the arrester and analyzing its arc-extinguishing ability. To establish an accurate representation of the arc plasma, the Magneto-hydrodynamic (MHD) theory is employed within a single discharge chamber. Subsequently, the arc motion, trajectory, and dynamic changes following an electrical breakdown event are evaluated. Additionally, the effects of discharge chamber dimensions and distance between electrodes on the arc behavior are explored. Finally, by considering the structural factors of the MCA, the dynamic arc parameters including current density, velocity, temperature gradient, and total heat flux are investigated. The simulation results reveal that the dynamic evolution of the arc in the discharge chamber is most affected by the change in distance between electrodes.
engineering, electrical & electronic
What problem does this paper attempt to address?