Abstract:With the increasing demand of renewable energy and recently research in smart DC microgrids, electric systems with high presence of power electronics are gaining momentum. One evidence are the ungrounded low voltage DC (LVDC) microgrids and their energy management, which are a key for high efficiency systems. However, they are difficult to protect against electrical faults, especially against ground faults, due to the commutation frequencies and the duality of AC and DC currents that provoke a lack of selectivity in conventional protection relays. In this field, this paper proposes a ground fault detection method that discerns between the affected zone (AC or DC) by sequentially switching a grounding resistor among the different neutral and midpoints of the system. The method is based on the frequency domain analysis of the voltage waveform measured on this grounding resistor. To corroborate the method, numerous simulations were performed obtaining satisfactory results.