Modeling and experiments for a CO2 ground-source heat pump with subcritical and transcritical operation

Wei Wu,Harrison M Skye,John J Dyreby,Harrison M. Skye,John J. Dyreby
DOI: https://doi.org/10.1016/j.enconman.2021.114420
IF: 10.4
2021-09-01
Energy Conversion and Management
Abstract:<p>CO<sub>2</sub>-based ground-source heat pumps (GSHPs) have the potential to be very environmentally friendly, since GSHPs operate with high energy efficiency, and CO<sub>2</sub> has no ozone depletion potential (ODP) and a low global warming potential (GWP). We developed a prototype CO<sub>2</sub> liquid-to-air GSHP to investigate its performance potential in residential applications. Further, we developed a detailed model of the system that simulates both cooling and heating operation; the model is the primary focus of this report. The model simulates both subcritical and transcritical operation since the system regularly operates near and above the critical temperature of CO<sub>2</sub> (30.98 °C) during heating and cooling operation. The model considered both the refrigerant-side thermodynamic and transport processes in the cycle, as well as the air-side heat transfer and moisture removal.</p><p>We performed cooling tests for the prototype CO<sub>2</sub> GSHP that included those from the International Standards Organization (ISO) 13256-1 standard for liquid-to-air heat pumps, as well as extended tests at additional entering liquid temperatures (ELTs). The model predicted the measurements within 0.5% to 6.7% for COP, 1.0% to 3.6% for total capacity, and 3.3% to 4.9% for sensible capacity. We compared the measured cooling performance to published performance data for a commercially-available R410A GSHP and found that for ELTs below 20 °C, the CO<sub>2</sub> GSHP has a higher cooling COP and total capacity than the R410A GSHP. At the 'standard' cooling rating condition (ELT 25 °C), the CO<sub>2</sub> GSHP COP was 4.14 and the R410A GSHP COP was 4.43. At 'part-load' conditions (ELT 20 °C) the CO<sub>2</sub> GSHP COP was 4.92 and the R410A GSHP COP was 4.99. In the future, the model can be used to investigate methods to improve the CO<sub>2</sub> GSHP performance to meet or exceed that of the R410A system over a wider range of ELTs; possible studies include replacing the electronic expansion valve (EEV) with an ejector, optimizing the charge, and optimizing the heat exchanger geometry and circuiting.</p>
energy & fuels,thermodynamics,mechanics
What problem does this paper attempt to address?