Monitoring the heating energy performance of a heat wheel in a direct expansion air handling unit

Miklos Kassai,Laith Al-Hyari
DOI: https://doi.org/10.1016/j.ijrefrig.2024.10.035
IF: 4.14
2024-11-07
International Journal of Refrigeration
Abstract:This study presents an on-site examination of the heating energy performance of a real ventilation system, running on the flat roof of a shopping complex building in Hungary. The main focus of this study is to delve into the heating energy efficiency of specific air handling elements, such as the air-to-air rotary heat wheel and the direct expansion heating coil supplied by a variable refrigerant volume outdoor unit under real operation conditions. Additionally, an investigation was carried out during the heating season to scrutinize the potential occurrence of CO 2 transfer from the exhaust airflow to the supply airflow within the heat wheel, which issue highlights a notable limitation of the heat recovery system. Based on the monitored and measured data, the energy saving impact of the heat wheel was 20.5 % on the electric power consumption of the variable refrigerant volume outdoor unit throughout the entire heating period, compared to operation without heat wheel. Furthermore, the relative average of CO 2 cross-contamination is recorded as 3.8 % in the investigated heating season.
engineering, mechanical,thermodynamics