Experimental investigation of a new CO 2 refrigeration system arrangement for supermarket applications

PAEZ Ana,Bénédicte BALLOT-MIGUET,Benoit MICHEL,Pascal TOBALY,Rémi REVELLIN,Ana PAEZ
DOI: https://doi.org/10.1016/j.ijrefrig.2024.03.010
IF: 4.14
2024-03-18
International Journal of Refrigeration
Abstract:A new position of an internal heat exchanger within the thermodynamic cycle is proposed to improve the performance of CO 2 refrigeration systems in warm climates, specifically in supermarket applications. The proposed configuration uses the saturated vapor from the liquid receiver to recover the heat that is rejected by a subcooler positioned after the gas cooler. This system results in a reduced evaporator superheat. This configuration is compared with a reference system. The experimental study is conducted on a CO 2 laboratory cooling system reproducing a commercial plant. The cooling capacity of the system is 30 kW. The water inlet temperature in the gas cooler (hot source) varies from 15°C to 35°C, while the mono-ethylene glycol outlet temperature of the evaporator (cold source) is fixed at -8°C. The setup is validated through an energy balance. Using a subcooler in this new position improves the coefficient of performance by 10.2 % under transcritical conditions and 6.3 % under subcritical conditions when compared with the reference system.
engineering, mechanical,thermodynamics
What problem does this paper attempt to address?