Warning Method for Ultimate Thermal Stress of Cable Terminal Based on Tailpipe Temperature Monitoring

Dongxin He,Qingjing Zang,Junda Li,Hongshun Liu,Zhe Xu,Qingquan Li
DOI: https://doi.org/10.1007/s42835-023-01503-1
2023-06-04
Abstract:The thermal stress at the interface of different materials becomes distorted during the thermal expansion of a cable terminal, leading to cracking and insulation failure. To give a warning of the ultimate thermal stress of cable terminal, this paper presents a warning method for the ultimate thermal stress of the cable terminal based on tailpipe temperature monitoring. Taking a 110 kV gas-insulated switchgear cable terminal as an example, the heat transfer model of the cable terminal is established under the working condition of a through-flow. The relationship between the temperature of the tailpipe, maximum thermal stress of the epoxy casing, and current-carrying capacity of the cable is established based on a data fitting method, the ultimate stress of the epoxy is taken as a threshold value for the detection and calculate the corresponding current-carrying capacity of the cable and temperature of the tailpipe. The results show that the thermal stress concentration in the cable terminal exceeds the limit when the monitoring temperature at the exposed tailpipe reaches 54.25 °C. If the relationship between the external temperature of the cable terminal and maximum thermal stress is known, warning of the ultimate thermal stress of cable terminal by monitoring the temperature of the tailpipe, providing theoretical support for the regulation of the current-carrying capacity of the cable.
engineering, electrical & electronic
What problem does this paper attempt to address?