Impact of Reverse Power Flow on Distributed Transformers in a Solar Photovoltaic Integrated Low Voltage Network

Issah Majeed,Nnamdi Nwulu
DOI: https://doi.org/10.2139/ssrn.4172636
2022-01-01
SSRN Electronic Journal
Abstract:Modern LV distribution system necessitates solar PV penetration. One of the primary concerns with this grid-connected PV system is overloading due to reverse power flow (RPF) which degrades the life of distribution transformers. This study investigates transformer overload issues due to RPF in a low-voltage (LV) network with high PV penetration. A simulation model of a real urban Electricity Company of Ghana (ECG) is investigated against various PV penetration levels by load flows with ETAP software. The impact of reverse power flow on distribution transformer loadings is examined for high PV penetration. Using the least squares method, simulation results are modelled in Excel software. Transformer backflow limitations are determined by correlating operating loads with PV penetration. At high PV penetration, the models predict reverse power flow into the distribution transformer, assuming no voltage violations. Interpolations from the correlation models show transformer backflow operating limits of 78.04KVA and 24.77% at the threshold of reverse power flow. These limits correspond to a maximum PV penetration limit of 88.30%. The results show that in LV networks with high PV penetration, distribution planners should decide on control schemes for deploying battery energy storage devices near substation transformers to prevent RPF into the substation transformer.