Evaporation heat transfer of carbon dioxide at low temperature inside a horizontal smooth tube

Jung-In Yoon,Chang-Hyo Son,Suk-Ho Jung,Min-Ju Jeon,Dong-Il Yang
DOI: https://doi.org/10.1007/s00231-016-1922-2
2016-10-14
Heat and Mass Transfer
Abstract:In this paper, the evaporation heat transfer coefficient of carbon dioxide at low temperature of −30 to −20 °C in a horizontal smooth tube was investigated experimentally. The test devices consist of mass flowmeter, pre-heater, magnetic gear pump, test section (evaporator), condenser and liquid receiver. Test section is made of cooper tube. Inner and outer diameter of the test section is 8 and 9.52 mm, respectively. The experiment is conducted at mass fluxes from 100 to 300 kg/m2 s, saturation temperature from −30 to −20 °C. The main results are summarized as follows: In case that the mass flux of carbon dioxide is 100 kg/m2 s, the evaporation heat transfer coefficient is almost constant regardless of vapor quality. In case of 200 and 300 kg/m2 s, the evaporation heat transfer coefficient increases steadily with increasing vapor quality. For the same mass flux, the evaporation heat transfer coefficient increases as the evaporation temperature of the refrigerant decreases. In comparison of heat transfer correlations with the experimental result, the evaporation heat transfer correlations do not predict them exactly. Therefore, more accurate heat transfer correlation than the previous one is required.
thermodynamics,mechanics