Fault classification on the hybrid transmission line system between overhead line and underground cable

Jittiphong Klomjit,Atthapol Ngaopitakkul
DOI: https://doi.org/10.1109/ifsa-scis.2017.8023263
2017-06-01
Abstract:This paper illustrates fault classification on hybrid transmission line. Current signals were analyzed by coefficients of discrete wavelet transform (DWT). Daubechies4 (db4) is employed as mother wavelet to decompose high frequency components from fault signals. In this paper, ATP/EMTP is used to simulate fault signal from current signals. Hybrid system between overhead line and underground cable of 115 kV from Provincial Electricity Authority (PEA-Thailand) system in case single circuit single conductor with overhead and underground was used as simulation case study. Various factors such as location of fault, fault type and fault angle have been taken into consideration. DWT is then applied on phase current and zero sequence signals using MATLAB software in order to obtain coefficient in scale 1 for further analysis. This value is mainly used to design algorithm for fault classification. Result obtained from the study is satisfactory.
What problem does this paper attempt to address?