Performance Enhancement by Using Wet Pad in Vapor Compression Cooling System

Maki H. Zaidan,Thamir K. Ibrahim,Aadel A. R. Alkumait
DOI: https://doi.org/10.5614/j.eng.technol.sci.2019.51.1.4
2019-02-28
Journal of Engineering and Technological Sciences
Abstract:Vapor compression cooling systems are widely used in hot and dry climates where the atmospheric temperature in summer reaches around 48 °C and the relative humidity can be below 20%. These cooling systems normally use environmentally friendly gases that do not harm the ozone layer. These systems work with high gas pressure, which consumes high energy and leads to a low coefficient of performance when compared to cooling systems that do not use an environmentally friendly gas. Theoretical and experimental studies have been conducted to find a suitable solution for the performance improvement of this type of cooling system. A possible solution is to lower the temperature of the air before it enters the condenser of the compression cooling system by passing it through a wet pad. The water evaporates due to the latent heat that is withdrawn from the wet pad. The air temperature is reduced to about 11 °C before it enters the condenser of the compression cooling system. This enhancement increases the cooling capacity of the vapor compression cycle by nearly 20% and increases the coefficient of performance by 15%, in addition to reducing the consumed electricity up to 15%. In conclusion, the proposed method of adding a wet pad can significantly enhance the performance of the vapor compression cooling system.
What problem does this paper attempt to address?