Abstract:Governing the rate of heat transport by condenser tubes in the passive containment cooling system (PCCS), the steam condensation over a vertical cylinder in the presence of air was investigated experimentally. The main objective of this study was to explore if the condensation heat transfer coefficient relies on the tube dimension, which has been a variable missed in most condensation models or has been embraced without experimental demonstration under phase change environments. The mean heat transfer coefficient was measured in the condensation test facility named JERICHO (JNU Experimental Rig for Investigation of Condensation Heat transfer On tube). The outer diameter of the condenser tube used in this study was set to 21.5 mm. The measured heat transfer coefficients were compared to those obtained from the 40-mm-O.D. tube, and a multiplier to correct the variation of the heat transfer coefficient with the tube diameter was proposed for its application to Lee correlation. The proposed correlation was further validated against another set of experimental data obtained from a separate test facility housing the 31.8-mm-O.D. tube.