A Modified Correlative Model for Condensation Heat Transfer in Horizontal Enhanced Tubes with R32 and R410A Refrigerants

Gangan Zhang,Dehui Du,Le Zhang,Yanlong Xiang,Wei Li,Jiapei Zhang,Jincai Du,David J. Kukulka
DOI: https://doi.org/10.3390/en16134883
IF: 3.2
2023-01-01
Energies
Abstract:An experimental study was performed that compared tube side condensation heat transfer characteristics of enhanced tubes (hydrophobic surface tubes (HYD), herringbone micro fin tube (HB), and a composite hydrophobic/herringbone (micro fin) tube (HYD/HB)) to the performance of a smooth tube (ST). The condensation heat transfer coefficient (HTC) was calculated from data that were recorded for smooth and enhanced tubes that had an outer diameter (OD) of 12.7 mm. Data were collected (as a function of mass flow rate) using a couple of refrigerants (R410A and R32), for saturated temperatures of 35 °C and 45 °C, with vapor qualities that ranged from 0.8 to 0.2. Several previously reported smooth tube HTC models were used to calculate values that could be compared to experimentally obtained HTC values. The correlation model that demonstrated the best accuracy (for the conditions considered) was then modified for use with the enhanced tubes from this study. Results from the modified correlation show differences with experimental values that ranged from −10% to +17%; the new modified correlation demonstrates high prediction accuracy. An accurate correlation allows the evaluation of enhanced heat transfer tubes for use in high-efficiency heat exchanger systems. The development of this new model is significant in the study of enhanced heat transfer.
What problem does this paper attempt to address?