Low-Voltage Ride Through Strategy for MMC With Y0/Y0 Arrangement Transformer Under Single-Line-to-Ground Fault

Xiaohe Wang,Xu Cai,Qing Chen,Bin Lin,Rui Xie
DOI: https://doi.org/10.1109/access.2021.3073950
IF: 3.9
2021-01-01
IEEE Access
Abstract:In the offshore wind farm high-voltage direct-current (HVDC) system, the power delivery capability of the onshore modular multilevel converter (MMC) decreases severely under grid fault, which makes the DC-bus voltage increase rapidly and threatens the safe operation of the system. This paper proposes a low-voltage ride through (LVRT) strategy for MMC with $text{Y}_{0}/text{Y}_{0}$ arrangement transformer under single-line-to-ground (SLG) fault. The influence of different transformer arrangements to the MMC under SLG fault is analyzed. On this basis, a power delivery capability enhanced method is proposed for MMC with $text{Y}_{0}/text{Y}_{0}$ arrangement transformer to take advantage of its control ability on zero sequence current. In addition, an optimized LVRT strategy based on resonant controller is proposed, which has simple control structure and can ride through the SLG fault without DC chopper. The offshore wind farm MMC-HVDC simulation system is established in PSCAD/EMTDC and simulation studies are conducted to validate the effectiveness of the proposed LVRT strategy.
computer science, information systems,telecommunications,engineering, electrical & electronic