Fault Ride-through Strategy for Integration of Permanent Magnet Direct-driven Wind Turbines via MMC-HVDC

Yang YU,Qian XU,Shengfeng YANG,Zheng XU
DOI: https://doi.org/10.13296/j.1001-1609.hva.2017.10.025
2017-01-01
Abstract:It is necessary to reduce the output power of wind farms connected by flexible HVDC when a severe AC fault occurs in the grid.In this way,the DC voltage of the HVDC system can be kept within the safe range.A control strategy is proposed for enhancing the fault ride-through capability of the MMC-HVDC system connecting permanent magnet direct-driven wind turbines to the grid.A controlled voltage drop in the wind farm AC system and a controlled reduction of wind turbines'output active currents are combined to achieve a fast power reduction.Meanwhile,DC voltage deviation control is adopted to limit the voltage increase of the wind turbine DC link.The results of simulations show that the DC side voltages of MMC and wind turbines can keep stable under balanced or unbalanced fault conditions.The whole system can achieve fault ride-through by employing the proposed strategy.
What problem does this paper attempt to address?