Delayed deformation of confinement buildings: 30‐Year in situ measured data and prediction with the next‐generation Eurocode‐2

Abudushalamu Aili,Jean‐Michel Torrenti,Francis Barre,Ludovic Caba
DOI: https://doi.org/10.1002/suco.202300665
2024-01-13
Structural Concrete
Abstract:Biaxially prestressed large concrete structures of the confinement building in nuclear power plants (NPPs) should meet the safety requirement for the extension of the service time. Long‐term delayed strains of concrete are one of the key factors determining the safety factor in these structures. This article presents 30‐year long in situ measurement results of strain evolution of confinement buildings in four different NPPs. The delayed strains are predicted at a material level using the next‐generation Eurocode‐2, and the influence of temperature as proposed by the fib model code 2010, making use of delayed strain characteristics of the corresponding concrete from a previous study. We found that the default law given in Eurocode underestimates the delayed strain. However, with the possibility of adjusting the shrinkage and creep laws, the prediction results fit with a good accuracy for the in situ measurement.
construction & building technology,engineering, civil
What problem does this paper attempt to address?