Abstract:A phase change material (PCM) based cooling storage unit was designed for the emergency cooling in an air-cooled modular data center to alleviate the need for UPS while improving the operation reliability. The cooling storage unit was integrated with the ceiling air conditioner in a modular data center with the advantages of simple structure and convenient installation. Experiments including both charging and discharging process of the cooling storage unit were carried out in the constant enthalpy environment. The experimental results showed that for a 42 U standard cabinet with the size of 800 × 600 × 2000 mm (Depth × Width × Height) and the power of 6 kW, the cooling storage unit could meet the emergency cooling demand for at least 300 s at the inlet wind speed of 1.5 m/s. To further extend the cooling period, the arcuate fins were installed on the surface of the PCM plates to improve the heat transfer performance. Compared with the smooth PCM plate, the unit with arcuate fins could extend the emergency cooling time by 342 s and decrease the charging time by 1850 s under the same operating condition.