Inferring ventilation rates with quantified uncertainty in operational rooms using point measurements of carbon dioxide: Classrooms as a case study

Joshua Finneran,Henry Burridge
DOI: https://doi.org/10.2139/ssrn.4581556
IF: 7.093
2024-03-02
Building and Environment
Abstract:We present a robust integral method to estimate the daily mean per-person ventilation rate Q ̄pp based on carbon dioxide (CO 2 ) concentration measurements in operational spaces, and limited other data. The method makes no assumptions regarding the ventilation provision throughout the day, nor requires the room to be in a steady state, nor the air within to be well-mixed. We demonstrate that several integral parameters remain reliably close to a value of unity, despite large variations in room conditions. Evaluating the likely distributions of integral parameters provides a method to quantify the uncertainty bounds and therefore assess the reliability of these ventilation estimates. Taking school classrooms as a case study, estimates of Q ̄pp based on measured CO 2 are shown to exhibit uncertainty bounds (of 95% confidence intervals) of approximately ± 24% if no other data than the classroom timetable is available. Deploying four CO 2 sensors within a classroom is expected to halve the uncertainty bounds to around ± 12%. Moreover, the framework presented herein evidences that when the same classroom experiences similar usage on two different days, the relative per-person ventilation rate achieved during these two days can be simply determined by the ratio of their integral excess CO 2 concentrations. These significant findings offer great scope to facilitate more reliable ventilation estimates, particularly from large-scale data sets of CO 2 measured in operational spaces, to better inform assessments of indoor air quality.
engineering, environmental,construction & building technology, civil
What problem does this paper attempt to address?