Modeling and Parameter Optimization of Grid-Connected Photovoltaic Systems Considering the Low Voltage Ride-through Control

Li Wang,Teng Qiao,Bin Zhao,Xiangjun Zeng,Qing Yuan
DOI: https://doi.org/10.3390/en13153972
IF: 3.2
2020-08-02
Energies
Abstract:The asymmetric faults often cause the power grid current imbalance and power grid oscillation, which brings great instability risk to the power grid. To address this problem, this paper presented a modeling and parameter optimization method of grid-connected photovoltaic (PV) systems, considering the low voltage ride-through (LVRT) control. The harmonics of the grid current under asymmetric faults were analyzed based on the negative-sequence voltage feedforward control method. The notch filter was added to the voltage loop to filter out the harmonic components of the DC bus voltage and reduce the harmonic contents of the given grid current value. The proportional resonant (PR) controller was added to the current loop. The combination of these two components could reduce the 3rd, 5th, and 7th harmonics of the grid current and the output power fluctuation. Then, the parameters of the inverter controller were identified by the adaptive differential evolution (ADE) algorithm based on the sensitivity analysis. The effectiveness of the proposed method was compared with two other strategies under the asymmetric grid faults. The suppression of DC bus voltage fluctuation, power fluctuation, and low-order harmonics of the grid current all had better results, ensuring the safe and stable operation of the PV plant under grid faults.
energy & fuels
What problem does this paper attempt to address?
The problem that this paper attempts to solve is the insufficient low - voltage ride - through (LVRT) capability of the grid - connected inverter in the photovoltaic (PV) system when an asymmetric fault occurs in the power grid. Specifically, when an asymmetric fault occurs in the power grid, a large number of negative - sequence components and harmonics will appear in the grid current. This will not only lead to unbalanced and oscillating grid current, increasing the risk of instability in power grid operation, but also cause problems such as DC bus voltage fluctuation and output power fluctuation, affecting the stable operation of the photovoltaic system. To meet this challenge, the paper proposes a modeling and parameter optimization method for grid - connected photovoltaic systems, which specifically takes into account the LVRT control strategy. By introducing a notch filter and a proportional resonant controller (PR Controller), this method aims to reduce low - order harmonics such as the 3rd, 5th, and 7th in the grid current and the fluctuation of output power, thereby ensuring the safe and stable operation of the photovoltaic power station in the case of power grid faults. In addition, the paper also identifies the inverter controller parameters through the adaptive differential evolution algorithm (ADE) to optimize its performance. These measures work together to improve the LVRT capability of the photovoltaic system when facing asymmetric faults in the power grid.