On the Transient Overcurrent Mechanism of Grid Forming Converter in Fault Recovery Stage

Boxin Liu,Xin Xiang,Yonghao Li,Yi Long,Tianling Shi,Huan Yang,Wuhua Li,Xiangning He
DOI: https://doi.org/10.1109/tpel.2024.3418044
IF: 5.967
2024-01-01
IEEE Transactions on Power Electronics
Abstract:The grid forming (GFM) converter may undesirably output a higher current during the recovery stage than fault duration due to its transient angle swing, which would cause the power devices to face the risk of overcurrent or even damage in both the fault stage and the recovery stage. In this letter, the current power angle plane is presented for the current trajectory description and the mechanism of the recovery overcurrent (ROC) issue is revealed through the proposed concept of critical recovery angle (CRA). On top of that, the power angle relationship in the critical ROC state is described in detail and the ROC boundary is further characterized accurately. Moreover, an analytical calculation method of CRA is proposed to identify whether the ROC phenomenon occurs, which is well validated by a series of experiments. The proposed method depicts the inherent relationship between the current behavior and power angle motion of GFM converters quantitatively and intuitively, and it may provide some new insights into the transient analysis and control optimization of GFM converters.