Influences of Center Frequency and Bandwidth on UHF PD Detection for Transformers

Guoli Wang,Yuan Bo Peng
2005-01-01
Abstract:The selections of center frequency and bandwidth are very important to detection, calibration and pattern recognition of ultra-high-frequency (UHF) partial discharge (PD) signals in transformers. In this paper, an UHF PD detection system and a typical PD models simulated system are developed to study the influences of center frequency and bandwidth on UHF PD detection for transformers. Experimental results show, the selected center frequency should be in the frequency range that the UHF component of PD signals is rich and the noise is not very strong, the bandwidth of the filters should be as wide as possible unless the noise goes high.
What problem does this paper attempt to address?