Research on Transformer Gas Relay Malfunctions Caused by External Short-Circuit Currents

Hao Liu,Chenguang Yan,Xiao Yang,Che Xu,Baohui Zhang,Yicong Chen,Shuyou Zhu,Shengjie Chen,Xianwu Zhou
DOI: https://doi.org/10.1109/asemd59061.2023.10369132
2023-01-01
Abstract:This digest introduces a sophisticated numerical model for studying transformer gas relay (GR) malfunctions during external short-circuit (SC) faults. The model captures electromagnetic and mechanical responses using the finite element method (FEM) for a 40 MVA/110 kV transformer. Additionally, a precise computational fluid dynamics (CFD) model based on the finite volume method (FVM) and dynamic mesh technique (DMT) simulates transient variations in the fluid field. The results reveal significant winding vibrations and fluid disturbances, leading to sustained oil surges into the GR, potentially causing GR malfunctions, transformer isolation, and power cuts.
What problem does this paper attempt to address?