High Sensitivity Differential Protection for AC Line in MMC-HVDC System

Qian Zhao,Haotian Cheng,Xiaodong Zheng,Zhongping Liu,Huaiyu Zhang,Yinjing Xiao,Haoran Liu,Huayanran Zhou
DOI: https://doi.org/10.1109/apap59666.2023.10348418
2023-01-01
Abstract:Due to the influence of MMC control mode, the differential protection of AC transmission line in MMC-HVDC system has low sensitivity. To solve this problem, a high sensitivity differential protection scheme based on phase correction is proposed. The phase offset affected by the control link is calculated and the additional phase Angle is obtained. The additional phase Angle is introduced in the calculation of differential protection. In view of different fault phases, positive and negative sequence current is used to correct the phase. The influence of MMC control strategy on differential protection is reduced. The scheme can effectively identify faults and has high sensitivity. At the same time, it can adapt to different operation modes of MMC and has strong resistance to transition resistance.
What problem does this paper attempt to address?