Research on DC Fault Clearance Speed of Hybrid MMC Full Bridge Submodule Ratio

Yili Han,Qingyu Wang,Peng Liu,Zongren Peng,Xin Tong
DOI: https://doi.org/10.1109/pset59452.2023.10346504
2023-01-01
Abstract:This article aims to investigate the impact of the proportion of full-bridge sub-modules on the interruption of fault current in a full-bridge/half-bridge hybrid MMC converter under DC faults. The full-bridge/half-bridge MMC converter has gained wide attention due to its ability to interrupt fault current like a full-bridge MMC, as well as the advantages of low cost and loss of a half-bridge MMC. By theoretical derivation, this article obtains the variation process of fault current for the hybrid MMC converter under DC bipolar short circuit faults and verifies the theoretical calculations through simulations in PSCAD/EMTDC. Both the theoretical calculation and simulation results indicate that with an increase in the proportion of full-bridge sub-modules, the peak value of fault current does not significantly increase, but the fault current interruption time decreases.
What problem does this paper attempt to address?