Study on Influence of Outdoor Airflow on Performance of Evaporative Cooling Composite Air-Conditioning System for Data Center

Haotian Wei,Zhiqiang Han,Chenguang Bai,Qi Fu,Xiangying Meng
2020-01-01
Abstract:Aiming at the large energy consumption of the air-conditioning system in the data center, an evaporative cooling composite air-conditioning system was proposed. This paper analyzes the impact of outdoor airflow on system performance parameters under different cooling requirements through system modeling and simulation. The results show that the increasing airflow of the outdoor unit increases the energy consumption of the fan, but helps to reduce the power consumption of the compressor and the refrigerant pump. Taking COP value as objective function, the optimum outdoor airflow is obtained. Under the 100, 80, and 60% rated cooling capacity of this system, the optimal outdoor airflow in the heat pipe mode are 2000, 1400, and 800 m3/h and in the vapor compression mode are 4000, 3600, and 2400 m3/h, respectively.