Experimental Investigation on a Pump-driven Two Phase Cooling Unit and Its Energy Saving Effect

Xuan Wang,Guoyuan Ma,Feng Zhou
DOI: https://doi.org/10.3969/j.issn.0253-4339.2017.02.082
2017-01-01
Abstract:Compared with the traditional vapor compression air conditioner,the pump-driven two phase cooling unit has a great potential in energy saving of data centers for it consumes less power and has a higher energy efficiency ratio when air temperature is low.However,insufficient control strategies not only hinder the improvement of performance,but also influence the accuracy of indoor temperature controlling,which limits the practical application.For a better application on small data centers,this paper designs a control system for the pump-driven two phase cooling unit,and studies its operating performance using in a small data center.This paper also fits the operating characteristic curves and makes an energy saving analysis.The results show that when the set point of indoor temperature is 22 ℃,the pump-driven system can fit the heat load well and get a good energy saving effect under the condition of an outdoor temperature of 10 ℃ or lower,and it can achieve at least a ratio of 26.77% on energy saving comparing with the existing air conditioner of the data center.