Development of gas pressurized composite air-conditioning unit and annual operation energy efficiency analysis

Wenxing Shi,Fei Wang,Deyong Huang,Zuojun Shi
DOI: https://doi.org/10.3969/j.issn.1009-8402.2017.02.003
2017-01-01
Abstract:Aimed at the all-weather air conditioning of data room,one composite air-conditioning unit which combines vapor compression refrigeration circulation with gas pressurized separation type heat pipe circulation is proposed.One composite air-conditioning prototype with cooling capacity of 10 kW is designed,and the performance test is carried out in the enthalpy method laboratory.The results show that when the temperature difference between indoor and outdoor reaches 20 ℃,the gas pressurized separation type heat pipe cycle can be used for the replacement of the conventional vapor compression refrigeration cycle as equal cooling capacity,and the energy-saving rate is about 8%;the energy efficiency ratio (EER) of the unit increases approximately linearly with the temperature difference between indoor and outdoor,and the energy-saving rate reaches 70% when the temperature difference between indoor and outdoor reaches 30 ℃;compared with the conventional vapor compression type air-conditioning unit in the data room,the annual energy efficiency ratio (AEER) of the pressurized composite air-conditioning unit is increased by 40%.This technology provides a new way for the low cost and temperature control of high energy efficiency for the high heating space,such as data center and information base station.