Operation performanceand energy-saving analysis of a pumped free cooling unit at an actual data center

Feng Zhou,Xuan Wang,Guoyuan Ma
2016-01-01
Abstract:A pumped free cooling unit using ambient energy was developed and in-stalled at an actual data center in a Beijing public agent.According to ongoing monitoring data,the operation EER of the unit was tested and analyzed.The fitting correlation be-tween EER and outdoor temperature was obtained,and the annual energy-saving rate be-fore and after reform was discussed and calculated.The results indicate that the operation EER increases with the decreasing outdoor temperature and the pumped free cooling unit works well. The operation EER and energy-saving rate can respectively reach 1 1 .88 and 22.7%.