Comparative Analysis on Operation Strategies of CCHP System with Cool Thermal Storage for a Data Center

Xu Song,Liuchen Liu,Tong Zhu,Tao Zhang,Zhu Wu
DOI: https://doi.org/10.1016/j.applthermaleng.2016.07.142
IF: 6.4
2016-01-01
Applied Thermal Engineering
Abstract:Combined Cooling, Heating, and Power (CCHP) systems with cool thermal storage can provide an appropriate energy supply for data centers. In this work, we evaluate the CCHP system performance under two different operation strategies, i.e., following thermal load (FTL) and following electric load (FEL). The evaluation is performed through a case study by using TRNSYS software. In the FEL system, the amount of cool thermal energy generated by the absorption chillers is larger than the cooling load and it can be therefore stored and reused at the off-peak times. Results indicate that systems under both operation strategies have advantages in the fields of energy saving and environmental protection. The largest percentage of reduction of primary energy consumption, CO2 emissions, and operation cost for the FEL system, are 18.5%, 37.4% and 46.5%, respectively. Besides, the system performance is closely dependent on the equipment selection. The relation between the amount of energy recovered through cool thermal storage and the primary energy consumption has also been taken into account. Moreover, the introduction of cool thermal storage can adjust the heat to power ratio on the energy supply side close to that on the consumer side and consequently promote system flexibility and energy efficiency. (C) 2016 Elsevier Ltd. All rights reserved.