Analysis of Icing-caused Dynamic Collapse of Transmission Towers in Shaoguan

Liqun Tang
2008-01-01
Abstract:In this paper,icing-caused damage of transmission lines in power grid of Shaoguan,China is investigated.Upon measuring the thickness of the ice covering 220 kV Pingtong transmission line,damage and collapse types of three neighboring towers(No.119 to No.121) are studied.Considering the relative positions of the three towers,it draws a conclusion that the destruction was mainly caused by local damage of tower under the heavy ice load on wire which led to dynamic collapse of the neighboring towers.Some advice to repair these destroyed towers and to further relevant research is proposed as well.