The Effect of Base Oil Aging on Conductivity of Electric Compound Grease

Zhaolin Ni,Zhidong Jia,Yuan Liu,Hongfeng Zhu,Zhengrong Chen,Yaohong Zhao,Zeyan Zhang,Xilin Wang
DOI: https://doi.org/10.1109/cieec58067.2023.10165767
2023-01-01
Abstract:The aging failure of electric compound grease in humid and hot environment will cause heat generation problems and affect the safe operation of the electric grid. Most of the aging of electric compound grease is caused by the failure of the base oil. thermal oxidative aging is the main factor affecting the life of electric compound grease. The type of base oil has a great influence on the life of the electric compound grease. In this article, we found that silicone electric compound greases are more thermally stable than hydrocarbon greases and The thermal stability of polydimethylphenyl silicone electric compound grease is higher than that of polydimethyl silicone electric compound grease. During the hot oxygen aging process, the contact resistance of the copper bar will first decrease and then increase. Electric compound greases with good thermal stability and low oil separation rate will keep the copper bar with a small contact resistance.
What problem does this paper attempt to address?