Comparative Investigation among Different Devices Used to Measure Post Arc Current in DC Interruption with Vacuum Interrupters

Qiang Tang,Shenli Jia,Zongqian Shi,Yongpeng Mo
DOI: https://doi.org/10.23919/ISDEIV55268.2023.10201187
2023-01-01
Abstract:Four types of devices were used to measure the post arc current of vacuum interrupters after forced current zero for DC interruption. Three of these devices are coils but each uses a different method to integrate di/dt. These are a passive integrator circuit, an active circuit and a digital integrator in a software. A forth device consists of a shunt and pairs of anti-parallel diodes which was introduced to verify the result given by the coils. We found that the current reconstructed by coils’ integrators have some inherent problems such as bias and phase shift. Such problems lead to uncertainty of current zero determination and it’s hard to tell how large the post arc current’s amplitude is. To validate the post arc current measured by coils, the forth device is used because resistive device has advantage of not needing integrator circuit nor digital integration. Strong oscillation due to parasite capacitance of diodes and stray inductance was observed but it actually doesn’t affect recognition of post arc current. We compared the results of measured post arc current using these four devices in DC vacuum interruption situations in order to find a reliable post arc current measuring method. Analysis of the coils’ working principles proves simple mathematical correction takes effect in giving correct post arc current from the biased original data.