Simulation Study on the Arc Extinguishing Performance of Eco-friendly HFO-1336mzz(E)Mixture Gas in a Load Switch

WANG Kai,ZHOU Ran,ZHANG Boya,LI Xingwen,CAO Minchuan,DENG Junwei,TANG Nian
DOI: https://doi.org/10.13336/j.1003-6520.hve.20220847
2023-01-01
Abstract:In order to reduce the use of SF 6 in power equipment,we investigated the application feasibility of eco-friendly SF 6 -alternative gas HFO-1336mzz(E) as the arc extinguishing medium in a 12 k V load switch.We established a two-dimensional magnetohydrodynamic simulation model and calculated the current interruption process in the puffer-type load switch.Moreover,we studied and compared the arc voltage,temperature field,airflow field distribution in the arc extinguishing chamber during the arcing period and the thermal interruption capability during the post-arc period for the 30%HFO-1336mzz(E)/CO 2 (0.12 MPa),30%HFO-1336mzz(E)/air (0.1 MPa) and SF 6 (0.1 MPa).The studies show that the arc quenching peak of HFO-1336mzz(E) gas mixtures is slightly greater than that of SF 6 ,and the arc diffusion in the axial direction is greater than that of SF 6 .When the current nearly exceeds zero,the arc temperature of HFO-1336mzz(E) gas mixtures is 1400 K lower than that of SF 6 .By analysis,the thermal interruption capability of 30%HFO-1336mzz(E)/CO 2 and 30%HFO-1336mzz(E)/air gas mixture can reach 95%and 96%that of SF 6 ,respectively.The results can provide reference for HFO-1336mzz(E) gas mixtures as arc extinguishing medium in medium voltage switchgears.