MMC-based General Calculation Method and Topology Optimization of DC Power Grid

BI Chaohao,SHI Yangang,FU Zhichao,CHEN Aobo,DENG Wenjun
DOI: https://doi.org/10.3969/j.issn.1673-7598.2023.04.014
2023-01-01
Abstract:The existing simplified calculation method of DC side short circuit in DC power grid is generally not applicable to symmetrical unipolar system,the rapid rise of fault current after short circuit fault leads to the blocking of converter station. A general calculation method and DC power grid topology optimization method suitable for symmetrical unipolar and bipolar connection DC power grid are proposed. Firstly,the characteristics of DC side pole-to-ground and pole-to-pole short circuit fault in different connection modes are analyzed. Secondly,a fault current calculation method suitable for DC power networks with different connection modes is proposed based on the impedance frequency characteristics,and a simplified index to evaluate the fault current level is obtained. This index can effectively evaluate the fault current level when the DC grid topology changes,thus realizing the topology optimization of the multi-terminal system and reducing the pole-to-ground fault current level. Finally,the accuracy and effectiveness of the proposed calculation method and simplified index is verified by electromagnetic transient simulation software.
What problem does this paper attempt to address?