Impedance Measurement Method for Obtaining the Accuracy of Current Transformers

Hongsen You,Mengying Gan,Dapeng Duan,Cheng Zhao,Yuan Chi,Weiqiong Song,Fengming Lv,Jinjun Xie,Jiansheng Yuan
DOI: https://doi.org/10.1007/978-981-99-0631-4_93
2023-01-01
Abstract:The accuracy acquisition method of the measurement current transformer (CT) given by the national metrological verification regulation JJG 313 is based on the comparison method with the standard transformer, that is, a transformer with two levels of accuracy higher than the tested product is selected as the benchmark, and the tested product accuracy is obtained by comparison. This method requires the standard CT, current sources, loads, etc. to form a complex detection platform. The method proposed in this paper to obtain the accuracy of CT by measuring the impedance parameters is based on its electromagnetic characteristics and equivalent circuit. The principle is simple and complete, and it is easy to implement with an impedance parameter measuring instrument, which omits the use of current source, standard CT and loads. The impedance method is easy for on-site detection, and avoids executing the comparison method in the verification center which is time-consuming and laborious.
What problem does this paper attempt to address?