Low-voltage Ride-through Control Strategy of Permanent Magnetic Synchronous Wind Turbine with Coordination of Super Capacitor Energy Storage and Chopper Circuit

WANG Yuxin,WANG Siyi,YANG Lihui,WANG Yifei,HU Zhilong,FAN Weiqiang,DANG Kai
DOI: https://doi.org/10.13296/j.1001-1609.hva.2023.04.024
2023-01-01
Abstract:In view of the low-voltage ride-through problem of permanent magnet synchronous wind turbine,a kind of low-voltage ride-through control strategy with the coordination of super capacitor energy storage and chopper circuit,combing with the advantages of both super capacitor energy storage and chopper circuit,is proposed. In case of fault of low voltage,the chopper resistor and super capacitor energy storage system are put into operation simultaneously at the DC link of the back-to-back converter to absorb jointly the unbalanced power due to the fault. After clearance of the fault,the super capacitor energy storage system feeds back the energy absorbed during the fault to the grid in accordance with the operation state of the grid side converter. The simulation results show that the proposed coordinated control strategy can,at the time of assuring to achieve reliably fault ride-through of the wind turbine,reduce the design capacity and cost of super capacitor and improve the utilization rate of wind energy.
What problem does this paper attempt to address?