New Low Voltage Ride-through Coordinated Control Schemes of Permanent Magnet Synchronous Generator Considering Rotor Speed Limit and DC Discharging Circuit Optimization

MENG Yongqing,WANG Jian,LI Lei,WANG Xiuli
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.24.003
2016-01-01
Abstract:Many countries' grid guidelines require that the grid-connected wind turbines must have low voltage ride through (LVRT) capability. Traditional LVRT coordinated control scheme saves all mismatching energy in the rotor of wind turbine during fault to keep DC bus voltage steady, which does not consider the possibility that the rotor speed may exceed the limit. Considering the requirements of grid guidelines in China, this paper provided detailed calculation of the question whether the rotor speed of permanent magnet synchronous generator (PMSG) would exceed the limit. The result shows that under this scheme many rotors' speed will exceed the upper limit when serious fault occurs. Considering this conclusion, this paper firstly proposed a discharging after storing scheme. This scheme could protect the rotor speed from exceeding the limit, but with which the rotor speed would reach the limit during serious fault. Furthermore, this scheme did not well optimize the impact current of discharging circuit. To deal with these problems, a new optimized coordinated control scheme which combines pitch adjustment and proportional discharging was finally proposed. The comparison simulation of the proposed LVRT coordinated control schemes shows the correctness of the theory and the effectiveness of control schemes.