Numerical simulation study on influence of cross-passage ventilation on spread of tunnel fire smoke

WANG Fangchao,ZHANG Duo,CHEN Changkun,JIAO Weibing
DOI: https://doi.org/10.11731/j.issn.1673-193x.2023.03.016
2023-01-01
Abstract:In order to explore the influence of cross-passage ventilation on the smoke spread of tunnel fire, the fire dynamics simulation software FDS was used to study the critical wind velocity of cross-passage, the temperature distribution of main tunnel and the height of smoke layer under different fire source locations.The results showed that within a certain range of fire source power, the critical wind velocity of tunnel cross-passage was proportional to 1/3 power of fire source power, and the farther the fire source was away from the cross-passage, the smaller the critical velocity was.When the fire source was located at the intersection and the cross-passage was ventilated with critical wind velocity, the temperature of smoke in the tunnel decreased obviously, but the smoke would quickly settle to below 2 m.When the fire source was 10 m and 20 m away from the intersection, the cross-passage ventilation would accelerate the downstream smoke settlement of fire source, and the smoke settlement velocity increased with the increase of the cross-passage ventilation rate.When the fire source was located at the intersection, the smoke settlement was dominated jointly by the cooling effect of cross-passage ventilation on the smoke and vortex effect, and when the fire source was located 10 m and 20 m away from the intersection, the smoke settlement was mainly dominated by the vortex effect.
What problem does this paper attempt to address?